Manufacturers

Kyoritsu 6011A Multi Function Tester

  • Model: KE 6011A
  • Shipping Weight: 1.1kg
  • Manufactured by: KYORITSU

RM4,900.00

Add to Cart:

Complies with IEC 61557

Designed to IP 54 Rating

Live circuit and wiring connection check LED's

Triple ranges insulation tests at 250, 500 and 1000V

Triple range loop and PSC tests 15mA test current at 200Ω/2000Ω range(No RCD Trip)

Phase angle selection on RCD ranges

Polarity switch for continuity tests

Auto-null facility for continuity tests

Earth probe for loop impedance testing on extraneous metalwork

Contact Voltage Reading

Test of a large kind of RCD's: Standard, Selective, AC and A
(DC sensitive breakers)

 

Continuity Testing

Measuring Ranges

20/200/2000Ω (Autoranging)

Open Circuit Voltage

>6V

Short Circuit Current

>200mA DC

Accuracy

|±(1.5%rdg+3dgt)

Insulation Testing

Measuring Ranges

20/200MΩ (Autoranging)

Test Voltage

250V 500V 1000V DC

Output Voltage on
Open Circuit

250V+40%-0%
500V+30%-0%
1000V+20%-0%

Rated Current

> 1mA

Accuracy

|±(1.5%rdg+3dgt)

Loop Impedance Testing

Rated Voltage

230V AC +10%-15% [50Hz]

Voltage Measuring Range

100~250V AC [50Hz]

Impedance Ranges

20/200/2000Ω

Nominal Test Current

25A (20Ω range) 15mA (200Ω range) 15mA (2000Ω range)

Accuracy

20Ω range ±(3%rdg +4dgt)
200Ω range ±(3%rdg +8dgt)
2000Ω range ±(3%rdg +4dgt)

PSC Testing

Rated Voltage

230V AC +10%-15% [50Hz]

PSC Ranges

200A (15mA Test Current)
2000A (25A Test Current)
20kA (25A Test Current)

Accuracy

PSC accuracy derived from measured loop impedance specification and measured voltage specification

RCD Testing

Rated Voltage

230V AC +10%-15% [50Hz]

Trip Current Settings

RCD × 1/2 : 10,30,100,300,500,1000mA
RCD × 1 : 10,30,100,300,500,1000mA
RCD × 5 : 10,30,100,300mA (on × 5 ranges max current 1A)

Trip Current Duration

RCD × 1/2 × 1: 2000ms 
RCD fast: 50ms

Accuracy

Trip current +10%-0% of test current at 230V
Trip time ±(1%rdg + 3dgt)

General

Safety Standard

IEC 61010-1 CAT.III 300V Pollution Degree 2
IEC 61557

Withstand Voltage

3700V AC for 1 minute

Power Source

LR6 (1.5V) × 8

Dimensions

130(L) × 183(W) × 100(D)mm

Weight

1100g approx.

Accessories

*KAPM10 
(Molded plug test leads for loop and RCD testing at sockets)
7122B (Test leads)
7132A (External earth probe)
Pouch for Test Leads
Shoulder Strap
Battery LR6 (1.5V) × 8
Instruction Manual

Optional Accessories

7133B (Distribution board test leads)

 

*

KAMP10(EU):European SHUKO plug
KAMP10(UK):British plug(13A) 
KAMP10 (AU):Australian plug
KAMP10(SA):South African plug